Lamp / ECG Configurator
Which lamp fits which ECG? Our lamp/ECG configurator will tell.
Read moreThis information can also be downloaded in pdf format from the Download Center.
In order to be able to fully utilise the advantages of the ECG, please observe the following installation and operating instructions.
Requirements:
Repuirements relatin to a lighting system with luminairs operated with electronic controls gear:
Further detailed guidelines may be found the technical handbooks QUICKTRONIC, QUICKTRONIC DIMMABLE, HALOTRONIC and POWERTRONIC.
1. Fault currents/FI switch
Problem:
For electronic control gear with protective earth (PE) both the high short duration in-rush current and the small leakage current from the interference suppression capacitors in the electronic control gear can trigger the residual current detector.
Solution:
2. Rating for automatic lin protection systems (MCBs)
In a choke/starter circuit, lamp ignition is slightly delayed; in an ECG circuit, all fluorescent lamps start simultaneously.
On switch-on at peak voltage, the storage capacitors of electronic contol gear causea high in-rush current for a few millisecongs.
In this case, the simultaneous charging of these capacitors in ECG operation can mean a higher system switch-on current than with a choke/starter circuit.
This reduces the maximum number of luminaires allowed per automatic line protection unit.
For example, the maximum number of luminaires allowed on an 10A automatic system reduces from 15 luminaires with 2x58W lamps with conventional control gear in a twin circuit to 8 ECG luminaires.
When using the values in the table please observe the following:
| Protector Rated current of circuit breaker |
Fluorescent lamp |
CCG single lamp | CCG twin lamp | QUICKTRONIC | ||
| uncomp. | parallel comp. | DUO | single lamp | twin lamp | ||
| 10 A | L 18W | 27 | 32 | 23 | 25 | 17 |
| OSRAM DULUX L, F 36 W |
23 | 32 | 23 | 25 | 17 | |
| L 38 W | - | 32 | 21 | 25 | 17 | |
| OSRAM DULUX L 55 W, L 58 W |
15 | 20 | 15 | 17 | 8 | |
| 16 A | L 18W | 43 | 51 | 37 | 41 | 28 |
| OSRAM DULUX L, F 36 W |
37 | 51 | 37 | 41 | 28 | |
| L 38 W | 37 | 51 | 34 | 41 | 28 | |
| OSRAM DULUX L 55 W, L 58 W |
24 | 33 | 24 | 28 | 13 | |
| 20 A | L 18W | 53 | 64 | 46 | 51 | 35 |
| OSRAM DULUX L, F 36 W |
46 | 64 | 46 | 51 | 35 | |
| L 38 W | 46 | 64 | 43 | 51 | 35 | |
| OSRAM DULUX L 55 W, L 58 W |
30 | 41 | 30 | 35 | 16 | |
| Protector Rated current of circuit breaker |
Fluorescent lamp |
QUICKTRONIC single lamp |
QUICKTRONIC twin lamp |
|
| 10 A | FH 14 W | 28 | 12 | |
| FH 21 W | 22 | 12 | ||
| FH 28 W | 12 | 8 | ||
| FH 35 W | 12 | 8 | ||
| 16 A | FH 14 W | 45 | 18 | |
| FH 21 W | 35 | 18 | ||
| FH 28 W | 18 | 12 | ||
| FH 35 W | 18 | 12 | ||
| 20 A | FH 14 W | 56 | 22 | |
| FH 21 W | 44 | 22 | ||
| FH 28 W | 22 | 15 | ||
| FH 35 W | 22 | 15 |
| Protector Rated current of circuit breaker |
Fluorescent lamp |
CCG single lamp | CCG twin lamp | QUICKTRONIC | ||
| uncomp. | parallel comp. | DUO | single lamp | twin lamp | ||
| 10 A | DL 18 W | 27 | 32 | 23 | 26 | 26 |
| DL 24 W, FQ 24 W, FC 22 W |
25 | 32 | 23 | 26 | 10 | |
| DL 36 W | 23 | 32 | 23 | 26 | 8 | |
| DL 40 W, FQ 39 W, FC 40 W |
- | - | - | 18 | 8 | |
| DL 55 W, FQ 54 W, FC 55 W |
- | - | - | 18 | 8 | |
| FQ 80 W | - | - | - | 8 | - | |
| 16 A | DL 18 W | 43 | 51 | 37 | 32 | 32 |
| DL 24 W, FQ 24 W, FC 22 W |
40 | 51 | 37 | 32 | 16 | |
| DL 36 W | 37 | 51 | 37 | 32 | 12 | |
| DL 40 W, FQ 39 W, FC 40 W |
- | - | - | 26 | 12 | |
| DL 55 W, FQ 54 W, FC 55 W |
- | - | - | 26 | 12 | |
| FQ 80 W | - | - | - | 12 | - | |
| 20 A | DL 18 W | 53 | 64 | 46 | 48 | 48 |
| DL 24 W, FQ 24 W, FC 22 W |
49 | 64 | 46 | 48 | 20 | |
| DL 36 W | 46 | 64 | 43 | 48 | 16 | |
| DL 40 W, FQ 39 W, FC 40 W |
- | - | - | 33 | 16 | |
| DL 55 W, FQ 54 W, FC 55 W |
- | - | - | 33 | 16 | |
| FQ 80 W | - | - | - | 16 | - | |
| Protector Rated current of circuit breaker |
Fluorescent lamp |
CCG single lamp | CCG twin lamp | QUICKTRONIC | ||
| uncomp. | parallel comp. | DUO | single lamp | twin lamp | ||
| 10 A | DS/E 5 W | 50 | 90 | - | 32 | - |
| DS/E 7 W | 50 | 90 | - | 32 | - | |
| DS/E 9 W | 55 | 90 | - | 32 | 20 | |
| DS/E 11 W | 50 | 90 | - | 32 | 20 | |
| 16 A | DS/E 5 W | 80 | 130 | - | 48 | - |
| DS/E 7 W | 80 | 130 | - | 48 | - | |
| DS/E 9 W | 90 | 130 | - | 48 | 28 | |
| DS/E 11 W | 100 | 130 | - | 48 | 28 | |
| 20 A | DS/E 5 W | 100 | 165 | - | 60 | - |
| DS/E 7 W | 100 | 165 | - | 60 | - | |
| DS/E 9 W | 110 | 165 | - | 60 | 34 | |
| DS/E 11 W | 120 | 165 | - | 60 | 34 | |
| Protector Rated current of circuit breaker |
Fluorescent lamp |
CCG single lamp | CCG twin lamp | QUICKTRONIC | ||
| uncomp. | parallel comp. | DUO | single lamp | twin lamp | ||
| 10 A | DD/E 10 W | 44 | 80 | - | 32 | 20 |
| DD/E 13 W | 44 | 80 | - | 32 | 20 | |
| DD/E 18 W | 38 | 55 | 30 | 26 | 20 | |
| DT/E 18 W | ||||||
| DD/E 26 W | 26 | 40 | 22 | 26 | 20 | |
| DT/E 26 W | ||||||
| DT/E 32 W | - | - | - | 20 | 10 | |
| DT/E 42 W | - | - | - | 12 | - | |
| 16 A | DD/E 10 W | 70 | 118 | - | 48 | 28 |
| DD/E 13 W | 70 | 118 | - | 48 | 28 | |
| DD/E 18 W | 60 | 88 | 80 | 32 | 28 | |
| DD/E 26 W | 42 | 66 | 36 | 32 | 28 | |
| DT/E 32 W | - | - | - | 28 | 16 | |
| DT/E 42 W | - | - | - | 18 | - | |
| 20 A | DD/E 10 W | 88 | 150 | - | 60 | 34 |
| DD/E 13 W | 88 | 150 | - | 60 | 34 | |
| DD/E 18 W | 76 | 110 | 62 | 48 | 34 | |
| DD/E 26 W | 52 | 82 | 46 | 48 | 34 | |
| DT/E 32 W | - | - | - | 34 | 20 | |
| DT/E 42 W | - | - | - | 22 | - | |
| Line protection switch |
PTU 70/230-240 | PT 150/230-240 N-2 | PT-DS 80/230-240 | |
| Trigger | B 10 | 10 | 5 | 8 |
| characteristic B | B 16 | 15 | 8 | 12 |
| (DIN VDE 0641) | B 20 | 20 | 10 | 15 |
| Siemens 5 SX.. | B 25 | 25 | 12 | 20 |
| Trigger | C 10 | 20 | 10 | 8 |
| characteristic C | C 16 | 30 | 16 | 12 |
| (DIN VDE 0641) | C 20 | 40 | 20 | 15 |
| Siemens 6 SX.. | C 25 | 40 | 25 | 20 |
| Line protection switch |
HTM 70 | HT 70 L | HT 70 LF | HT 80 L | HTM 105 | HT 105 L | HT 120 LF | HT 150 L | HT 210 L | |
| Trigger | B 10 | 37 | 37 | 37 | 19 | 23 | 15 | 13 | 8 | 5 |
| charact- | B 16 | 59 | 59 | 59 | 30 | 38 | 24 | 21 | 13 | 9 |
| eristic B | B 20 | 74 | 74 | 74 | 38 | 47 | 30 | 27 | 16 | 11 |
| B 25 | 92 | 92 | 92 | 47 | 59 | 38 | 34 | 26 | 14 | |
| Trigger | C 10 | 37 | 37 | 37 | 27 | 23 | 21 | 20 | 14 | 9 |
| charact- | C 16 | 59 | 59 | 59 | 43 | 38 | 34 | 32 | 22 | 15 |
| eristic C | C 20 | 74 | 74 | 74 | 54 | 47 | 43 | 40 | 28 | 19 |
| C 25 | 92 | 92 | 92 | 67 | 59 | 53 | 50 | 34 | 24 | |
The diagram above shows the wiring for luminaires or luminaire groups in 3-phase circuits and with a common neutral conductor.If the common neutral conductor is interrupted in a 3-phase star configuration and voltage is present, then luminaires or groups of luminaires operated with electronic control gear may be exposed to unacceptably high voltages and the ECG itself may be destroyed.
3. ECG in 3-phase operation
- Overvoltage / undervoltage / no neutral conductor
Important:
4. ECG in emergency lighting systems with d.c. voltage
| Permitted battery voltage | upper limit | lower limit |
| QUICKTRONIC INSTANT START | 264 V | 154 V |
| QUICKTRONIC PROFESSIONAL | 264 V | 154 V |
| QUICKTRONIC SHORT | 264 V | 176 V |
| QUICKTRONIC DE LUXE dimmable | 276 V | 154 V |
| QUICKTRONIC | 254 V | 176 V |
| QUICKTRONIC FH (T5) | 264 V | 176 V |
| QUICKTRONIC FQ (T5) | 264 V | 176 V |
| DULUXTRONIC | 254 V | 176 V |
| HALOTRONIC | 235 V | 154 V |
| POWERTRONIC | Not authorised for DC voltage operation | |
| Switch-on times | in permanent circuit Supply is switched from AC to DC |
Emergency luminaires are switched on from cold |
| QUICKTRONIC INSTANT START | < 0.3 sek. | < 0.3 sek. |
| QUICKTRONIC PROFESSIONAL | < 0.5 sek. | < 2 sek. |
| QUICKTRONIC SHORT | < 0.5 sek. | < 2 sek. |
| QUICKTRONIC DE LUXE dimmable | < 0.5 sek. | < 0.5 sek. |
| QUICKTRONIC | < 0.5 sek. | < 2 sek. |
| QUICKTRONIC FH (T5) | < 1 sek. | < 2 sek. |
| QUICKTRONIC FQ (T5) | < 0.5 sek. | < 2 sek. |
| DULUXTRONIC | < 0.5 sek. | < 2 sek. |
| HALOTRONIC | < 0.5 sek. | < 0.5 sek. |
| POWERTRONIC with hot re-ignition ignites the hot-cathode lamp again within 5 seconds. If POWERTRONIC is switched on from a cold state, it will take 1-2 minutes until the lamp attains 70 % luminous flux. |
||
5. Power factor / correction
The power factor for an electrical load is the ratio of effective power (Pactual = voltage x actual current) to apparent power (Papparent = voltage x effective current). to apparent power (Papparent = voltage x current). This value is affected both by the phase displacement cos j between current and voltage and also the current distortion
In contrast to conventional control gear (inductive, 50 Hz) with ECG (high frequency) there is virtually no phase shift ( = 0,95)with electronic control gear (high frequency).
The harmonic content of the line current is strictly controlled by national and international regulations (EN 61.000-3-2, IEC 1.000-3-2).
OSRAM ECG have integrated an active, fully electronic harmonic filter for this purpose which ensures a value for of more than 0.95 and hence a power factor
greater than 0.9.
top
6. Permitted cable length
QTIS, QTP and QTS:
When ECGs are is used in luminaires the cables, if correctly routed within the luminaires, produce little interference. When ECGs are used in master-slave circuits the aximum permissible cable length between the electronic control gear and the lamp is 3m.
(for more detailed information see the QUICKTRONIC product guide)
QUICKTRONIC for OSRAM DULUX L and OSRAM DULUX T/E, D/E, S/E:
To guarantee reliable operation, the maximum permissible cable length between electronic control gear and the lamp must not exceed 3m. The radio interference levels which occur in each case depend on the length and routing of the lamp cables. In the event of any doubt, we recommend that interference suppression measurements be taken (With QUICKTRONIC for OSRAM DULUX D/E and T/E), higher levels of radio interference can be expected with cable length in exdcess of 0.5m.
HALOTRONIC:
Maximum 12 V low-voltage line lengths
The maximum 12 V line length must be less than 2. to comply with radio interference limit values (this means that luminaires ccan be installed within a radius of 2m). 1mm² is recommended as the minimum cable crossection.
Cable routing:
The supply cable should not be routed along side the casing of the HALOTRONIC nor along side the highfrequency 12V secondary cable.
This avoids highfrequenzy interference on the supply cable.
Intruments for secondary voltage measurement:
An instrument for secondary voltage meansurement must be a true RMS meter and have a bandwidth >= 250kHz (-3dB). Any other instrument will give incorrect measurements.
POWERTRONIC:
The maximun cable length between the lamp and POWERTRONIC depends on the type of cable and how it is routed. The figures on the type of cable and how it is routed. The figueres shown in the table below can be used as guidelines
| PTU 35/230-240 | 3 m between lamp and POWERTRONIC |
| PTU 35/230-240 L | 3 m between lamp and POWERTRONIC |
| PTU 70/230-240 | 3 m between lamp and POWERTRONIC |
| PT-DS 80/230-240 | 0,5 m between lamp and POWERTRONIC |
7. Faults in infrared control/transmission
Fluorescent lamps have an emission in the wavelength range which is also used for infrared transmission and which can be affected by the lamp. Since the IR receivers used are largely non-selective, faults can arise in the IR if IF from the lighting system reaches the receiver. The IR transmitted by the fluorescent lamp is modulated with double the operating frequency (20 - 50kHz). Faults arise if the signal also operates in this frequency range. POWERTRONIC and HALOTRONIC are an exception to this rule since they do not couse any disturbance to infrared systems
IR remote control:
Control systems operating at a suitably high carrier frequency (400 - 1500 kHz) can be opertated without problems.
Sound transmission:
Up to now the carrier signal frequency for sound transmission has been 95kHz and higher, which has led to serious disturbances from the 3ed, 5th and 7th harmonics of the ECG operatin frequency ranges (30 to 45kHz in normal mode and up to 100kHz with dimming). Headphone manufacturers have adopted higher and higher frequencies such as 2,3MHz and 2,8MHz to remedy this situation.
Simultaneous interpreting systems also operate in the 95kHz to 250kHz range so it is best not to use the first six transmission channels, particularly channel 1, of the 32 trannsmission channels available since these are likewise affected by the harmonics of the basic ECG frequencies.
High-frequency ripple control:
The carrier frequencies used are around 120kHz. Transmission can be adversely affected by radio interference uppression capacitors which are included in all ECGs or in other electronic loads, such as the power supplies of PCs.
Paging systems:
be used. When inductive paging systems are used 825 - 40kHz) reliable operation is not possible.
top
9. Luminaires with ECG
The following general points apply to luminaires with electronic control gear:
10. Ambient and ECG temperatures
The temperature ranges specified for the relevant control gear must be maintained to enable the ECGs to operate reliably. Generally speaking, lower operating temperatures extend the life of electonic control gear. Where ECGs are built into luminaires the measuring pont temperature Tc on the casing is the crucial parameter. The maximum permissible value specified for the ECG concerned must not be exceeded.
top
11. ECG for outdoor luminaires
When using electronic control gear in outdoor luminaires it must be remembered that the electronic control gear may be exposed to humidify, depending on the luminaire. Basically the protection type of the lamp (IP ..., to DIM 40050/IEC 529) determines whether standard ECGs or special ECGs can be incorporated.
12. Life span and reliability of electronic control gear systems
The failure rate of electronic componets depends not only on the component specification and quality but also very considerably on the operating temperature.
OSRAM´s ECGs are designed so that at a maximum permissible ECG temperature (tc max) a lailure rate of fewer than 2 per 1000 ECGs per 1000 hours of operation can be expected. This corresponds to an ECG life of 50.000h at a percentage ECG failure of less than 10%. (HALOTRONIC HTM Mouse: failure rate 5 per 1000 ECGs per 1000 hours of operation or a life of 30.000 hours at a percentage ECG failure of 10%). A reduction in the operating temperature by 10 degrees can halve the failure rate. By using hight quality components and systematic quality assurance measures, OSRAM can give a gaurantee against material or manufacturing faults of 12 months from the start of operation but not more than months afer the date of manufacture of the ECG. Within this period the product will normally be replace or a credit note issued; further claims will not be entertained unless there is legal obligation.